In a fire, a siren only tells people that something is wrong; it does not tell them what to do. A voice evacuation system directs people to the right exit with an intelligible spoken message. Day to day, the same infrastructure carries paging and background music.

What does EN 54 cover?

EN 54 is the European family of standards for fire detection and alarm systems. Three parts matter for voice evacuation: the central equipment, the loudspeakers and the power supply. Products certified to these parts are tested to keep working in fire conditions.

PartEquipment covered
EN 54-16Voice alarm control and indicating equipment (central unit, amplifiers)
EN 54-24Voice alarm loudspeakers
EN 54-4Power supply and battery backup

Intelligibility

In a voice evacuation system the measure is intelligibility, not loudness. The speech transmission index (STI) is a value between 0 and 1; evacuation systems usually aim for at least 0.50. In reverberant spaces such as terminals and atria that target is only reached with the right loudspeaker type and layout, which is why the design is simulated and then verified by measurement at handover.

Points to watch in design

Request a quote →

Related pages

Terms on this page

Voice alarm (EN 54)Speech intelligibility (STI)

Let’s plan your project together.

Whether you have architectural drawings, a specification or just an idea, our engineering team is ready for a survey and concept design.

Pressing the button opens your e-mail app with these details; sending is up to you.

Request a quoteCall